714/001/115

  • Availability: In Stock

Networking & System Architecture

  • Supports network configurations of up to 16 loops total, including:
    • 16 × 1-loop control panels
    • 8 × 2-loop control panels
    • 4 × 4-loop control panels
    • or any mixed configuration, not exceeding 16 loops in total
  • True peer-to-peer, fault-tolerant network topology ensuring high system availability and resilience
  • Network fully compliant with BS 5839-1

Configuration & Programming

  • PC-based configuration software (supplied as standard with control panel)
  • Programmable logic functions including Event Logic and Input/Output (I/O) cause-and-effect configuration
  • Optional multi-language support for system programming and interface

Detection & Alarm Management

  • Supports up to 80 fire zones, configurable with or without LED indication
  • Coincidence detection and alarm verification algorithms for false alarm reduction
  • Adjustable detector sensitivity profiles (e.g., day/night mode operation)

Control & Timing Functions

  • Integrated 7-day programmable timers
  • Class change input function for external control (e.g., schools, public buildings)

Monitoring & Diagnostics

  • Comprehensive event logging with timestamped records
  • Onboard diagnostic tools for system status monitoring and fault analysis

Zone & Indication Features

    • Enhanced zone indication supporting up to 160 LEDs
    • Flexible zone referencing scheme for customized system mapping
    • Remote LED indication with Event Logic integration