Zone Interface Module Features
- Interface for connecting a zone of conventional (non-addressable) detectors to an analogue addressable fire alarm system
- Built-in short-circuit isolation for staged system installation without loss of protection
- Open-circuit and short-circuit fault monitoring
- Tri-colour status LED indication
- Zone powered via addressable loop or external 24 VDC power supply
- Remote reset capability for the conventional zone
- External power supply monitoring
- External fault input
- Certified to EN 54-17 and EN 54-18 with LPCB approval and VdS certification
- DIN rail mountable, consistent with other system modules
- Supports extended power supply range down to 18 VDC, 60 mA (with external PSU)